Cubicle Automatic fire extinguisher

Overview of the proposal

Automatic fire fighting equipment is installed in small spaces to prevent fire spreading by extinguishing fires in cubicles in station transformers.

Background of the proposal

Fires need to be put out in their early stages to prevent spread of secondary damage due to fires in cubicles to operate switches, circuit breakers, gauges, etc. safely for controling distribution systems, distributing electric power, making and breaking circuits, staying safe, and reading electric meters. The necessity of fire fighting equipment with latest fire extinguishing agents which never damage electronic facilities in operation when extinguishing fires has come to the fore.

Tray Cable
Fire safety standards
Surface fire Fire in deep parts
Fires break out on the surface of combustibles. Fires break out in combustibles
Fires break out on surface of the like oil. Fire from combustible combustible materials such as wood or fibers
  • The first fire breaks out on the surface. And as heat is transferred to deep parts, the second fire breaks out in them.
  • When people smoke, fires break out as inner parts burn with the surface.
  • Fire with heat like lumber, textile, and electrical cable.
NOVEC 1230 & Features of gas fire extinguishing agents
NOVEC - 1230 Gas system
There is few evaporation heat Evaporation heat is high
The agents can easily be applied to open areas with enclosed fire zones The gas system can just be applied to enclosed fire zones
Additional agents are not required because
there is no need of calculating openings
Fires cannot be extinguished in case of a lot of openings
Time to release fire extinguishing agents is 90 seconds Dangers of reignition are exposed because time to
release fire extinguishing agents is 15 seconds
hey are suitable for fires of deep parts because they extinguish fires like water. The gas system is unsuitable for fires of deep parts.

* Gas fire extinguishers can just be used in enclosed areas. But Novec 1230 can be applied to open.

NOVEC 1230 Insulation
Novec1230 has the electrically excellent dielectric behaviour in both of liquids and
gas so that it is never damaged even though it is sprayed on electric equipment or
electronic facilities. Gaseous voltage breakdown 16kV,
- 1atm, 21℃, 2.7mm The electrode gap conditions
- 2.3 times higher than those of N2 gas.
- Drippy voltage breakdown 48kV
Dielectric Strength¹(kV)
Novec 1230 Vapour 16 2.3 times that of dry nitrogen
Gaseous mixture 5 vol% Novec 1230 in air 9.2 1.4 times that of air
Novec 1230 liquid 48

¹According to a method consistent with ASTM D877

Environment regulation
Environmental Properties of Halon 1310 and Alternatives
Properties Halon 1301 Novec 1230 HFC - 125 HFC - 227ea HFC - 23
Ozone Depletion Potential(ODP) 12.0 0.0 0.0 0.0 0.0
Global Warning Portential - IPPC2001¹ 6,900 1 3,400 3,500 12,500
Atmospheric Lifetime(Years) 65.0 0.014 29.0 33.0 260
SNAP(Yes / No) N/A Yes Yes Yes Yes

¹IPPC Intergovernmental Panel on Climate Change.